DF-CH1 Chicago Illinois Data Center General Information
![]() Bandwidth is measured using the 95th percentile (5 minute samples). ![]() ![]() |
The Zio Inc.
Global IP Network provides your company with the reliability and
performance needed to keep your infrastructure connected. Zio
Inc. operates redundant network nodes in all
Infrastructure Colocation facilities. With multiple 10 gigabit
connections to both carriers and the ServerCentral backbone, every
facility can provide the rock solid reliability and redundancy our
customers require. Using the best technologies from Juniper Networks and Cisco Systems, our network is designed without compromise for optimal performance and availability. The Zio Inc. Global IP Network provides service in North America, Europe and Asia. Facilitating hundreds of private peering sessions with other networks, we can deliver your data to its final destination as quickly and efficiently as possible. ![]() |
Facility Provider: | DuPont Fabros Technology, Inc |
Address: | 2200 Busse Rd., Elk Grove Village, IL 60007 |
NPA-NXX: | 847-787 |
Location Orientation: | 8 miles from
O'Hare airport, 27 miles from Midway airport, near I-90 expressway |
Commissoned: | 2008 |
Building Area: | 485,000(sq ft) gross - 221,000(sq ft) raised floor |
Parking: | 518 spots onsite |
Computer Room Specifications (Per Room)
Raised Floor Space: | 10,000 square feet (approx.) |
Colocation Space: | 6,200 square feet |
Electrical Capacity: | 1,300kW of critical load |
Power Density: | 210 watts/sqft, up to 12kW/cabinet supported |
Floor Load Capacity: | 450psf |
Building Type: | Single story, raised floor |
Raised Floor Height: | 42" |
Fire Suppression: | Laser-based
Very Early Smoke Detection (VESDA) Pre-action zoned dry-pipe system |
Redundancy: | N+2 on critical systems |
Facility Information
Primary Voltage: | 34.5kV |
# of Utility Feeders: | 2 |
# of Power Transformers: | 8 |
UPS: | 16 - 1,300kW rotary powered systems |
Standby Power: | 16 - 2,250kW diesel generator systems |
Fuel Capacity: | 100,000 gallons of diesel |
Cooling System: | 8 - 1,150 ton centrifugal chillers |
Thermal Energy Storage: | 500,000 gallons of chilled water |
Data Pathways: | 2 diverse fiber vaults for redundant carrier points of entry |
Roof Access: | Available |
Loading Dock: | 4 enclosed and heated bays, hydraulic dock levelers |
Office Space: | Up to 40,000
square feet of contiguous space available in attached building |
Security
Building and Perimeter: | Bullet-resistant
protection at security check-in and level III walls and doors |
Security Staff: | 24/7/365 staffing with at least 2 officers |
Access Control: | Dual-factor authentication system (keycard + biometrics) |
Alarm System: | Yes |
CCTV: | Camera surveillance archived onsite and offsite |